Индуктивный датчик Inductive sensor NBN3-F31K2M-E8-B13-S-3G-3D Pepperl+Fuchs
Производитель | Pepperl+Fuchs |
Описание товара
General specifications | ||
---|---|---|
Switching function | 2 x normally open (NO) | |
Output type | PNP | |
Rated operating distance | 2.5 mm | |
Installation | for non-flush mounting | |
Output polarity | DC | |
Assured operating distance | 0 ... 1.5 mm | |
Output type | 4-wire | |
Nominal ratings | ||
Operating voltage | 10 ... 30 V | |
Switching frequency | 0 ... 100 Hz | |
Hysteresis | typ. 5 % | |
Reverse polarity protection | all connections | |
Short-circuit protection | pulsing | |
Voltage drop | &le 3 V | |
Operating current | 0 ... 100 mA | |
Off-state current | 0 ... 0.5 mA typ. 0.1 µA | |
No-load supply current | &le 25 mA | |
Functional safety related parameters | ||
MTTFd | 490 a | |
Mission Time (TM) | 20 a | |
Diagnostic Coverage (DC) | 0 % | |
Electrical specifications | ||
Connection | Valve circuit | |
Power | voltage: 10 ... 32 V current: max. 240 mA | |
Ambient conditions | ||
Ambient temperature | -40 ... 75 °C (-40 ... 167 °F) , restriction for use in hazardous area, see instruction manual | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Mechanical specifications | ||
Connection (system side) | M20 x 1.5 cable gland , ground connection with earthing screw only for wire cross-section 4 mm2, use solid wire or stranded wire with wire end ferrule | |
Connection (valve side) | screw terminal , Cable gland M20 x 1.5 | |
Housing material | rugged polycarbonate (PC) + GF 10% , optimised for outdoor use | |
Degree of protection | IP67 additional degree of protection IP66/IP69K with BT65-F31K2-RG-EN-01 and SH-F31K2-B13 | |
Terminal assembly | ||
Number | 10 | |
Connection type | For connection of copper wires with 7 mm dismantle length Tightening torque 0.5 ... 0.6 Nm | |
Type | Screw terminal block, pluggable | |
Terminal capacity | Conductor cross-section 0,25 ... 2,5 mm2 , flexible/rigid For Multiple-wire connection: two wires of equal cross-section per 0.25 ... 1 mm2 | |
Tightening torque, fastening screws | 2 Nm | |
Tightening torque, housing screws | 1.5 Nm | |
Tightening torque, earthing screw | 1.5 Nm | |
Tightening torque, cable gland | max. 4 Nm | |
Tightening torque, stopping plug | 2 Nm | |
Equipment protection level Gc (nA) | ||
Certificate | PF 15CERT3754 X | |
Equipment protection level Dc (tc) | ||
Instruction | Manual electrical apparatus for hazardous areas | |
Device category 3D | for use in hazardous areas with combustible dust | |
Certificate | PF 15CERT3774 X | |
CE marking | [*PD-Z02586A*] | |
ATEX marking | II 3D Ex tc IIIC T80°C Dc The Ex-related marking can also be printed on the enclosed label. | |
Standards | EN 60079-0:2012+A11:2013, EN 60079-31:2014 Protection by enclosure tc Some of the information in this instruction manual is more specific than the information provided in the datasheet. | |
General | The corresponding datasheets, declarations of conformity, EC-type examination certificates, certifications, and control drawings, where applicable (see datasheets), form an integral part of this document. These documents can be found at www.pepperl-fuchs.com. The maximum surface temperature of the device was determined without a layer of dust on the apparatus. Some of the information in this instruction manual is more specific than the information provided in the datasheet. | |
Installation, commissioning | Laws and/or regulations and standards governing the use or intended usage goal must be observed. If the Ex-related marking is printed only on the supplied label, then this must be attached in the immediate vicinity of the sensor. The sticking surface for the label must be clean and free from grease. The attached label must be legible and indelible, including in the event of possible chemical corrosion. After opening the housing, you should check that the seal is in the correct position and is clean and intact before closing the housing again. Seal any openings on the housing not in use, using the stainless steel stopping plugs supplied. No other devices should be used to seal the openings. The stopping plugs made of plastic must no longer be used. | |
Maintenance | No changes can be made to apparatus, which are operated in hazardous areas. Repairs to these apparatus are not possible. After opening the housing, you should check that the seal is in the correct position and is clean and intact before closing the housing again. | |
Special conditions | ||
Maximum operating current IL | The maximum permissible load current must be restricted to the values given in the following list. High load currents and load short-circuits are not permitted. | |
Maximum operating voltage UBmax | The maximum permissible operating voltage UBmax must be restricted to the values given in the following list. Tolerances are not permitted. | |
Maximum permissible ambient temperature TUmax | dependant of the load current IL and the max. operating voltage UBmax Information can be taken from the following list. | |
at UBmax=30 V, IL=100 mA | 60 °C (140 °F) | |
Maximum values of the valve circuit | UV = 32 V IV = 240 mA | |
Protection from mechanical danger | The sensor must not be exposed to ANY FORM of mechanical danger. If you use the protective cover SH-F31K2-B13 and the actuator with protective cover BT65-F31K2-RG-EN-01, it is ensured that the device is sufficiently protected in accordance with IEC/EN 60079-0. If the protective cover becomes damaged, replace the protective cover. | |
Protection from UV light | The sensor and the connection cable must be protected from damaging UV-radiation. This can be achieved when the sensor is used in internal areas. If you use the protective cover SH-F31K2-B13 and the actuator with protective cover BT65-F31K2-RG-EN-01, it is ensured that the device is sufficiently protected in accordance with IEC/EN 60079-0. If the protective cover becomes damaged, replace the protective cover. | |
Electrostatic charge | Electrostatic charges must be avoided on the mechanical housing components. Dangerous electrostatic charges on the mechanical housing components can be avoided by incorporating these in the equipotential bonding. Sliding contact discharges must be avoided. Avoid electrostatic charges that can cause electrostatic discharge when installing or operating the device. Information on electrostatic hazards can be found in the technical specification IEC/TS 60079-32-1. Do not attach the nameplate provided in areas where electrostatic charge can build up. | |
Lead insertion | If cable glands are required for the installation then the following points must be observed: | |
Plug connector | The plug connector must not be withdrawn under voltage. The proximity switch is identified as follows: WARNING - DO NOT SEPARATE WHEN ENERGIZED. With the plug connector disconnected, soiling of the internal area must be prevented.(i.e. the area that is inaccessible when the connector is inserted) | |
General information | ||
Use in the hazardous area | see instruction manuals | |
Category | 3G 3D |
Характеристики
Производитель | Pepperl+Fuchs |
Важная информация
Все информационные материалы, представленные на сайте, носят справочный характер и не могут в полной мере передавать достоверную информацию о свойствах и характеристиках товара.
Фотография на сайте служит дополнительным источником для определения совместимости запчастей с Вашим оборудованием, и не может являться основным. Основной источник по совместимости запчастей - актуальная документация производителя оборудования, из которой значимой информацией для заказа являются: название запчасти и каталожный номер.
Запасные части и комплектующие подбираются самостоятельно покупателем строго по каталожным номерам из официальных деталировок производителей. В случае, если номенклатура товара совпадает с фактически поставленной, но не подходит на оборудование - в ее замене или возврате может быть отказано.
Цены на сайте имеют информационный характер и могут отличаться от цен в коммерческом предложении.
Производитель | Pepperl+Fuchs |