Адаптер Bullet WirelessHART Adapter WHA-BLT-F9D0-N-A0-Z0-Ex1 Pepperl+Fuchs
Производитель | Pepperl+Fuchs |
Описание товара
Supply | ||
---|---|---|
Rated voltage | 7 ... 30 V DC | |
Rated current | < 1 mA , max. 25 mA | |
Electrical specifications | ||
Output rated operating current | 3.2 ... 25 mA | |
Supply | loop power for field devices voltage: 1 ... 2.5 V DC, adjustable in steps of 0.5 V | |
Input | ||
Connection | - 5 wires, 600 mm long, exiting from male thread NPT1/2 - 1 external grounding point | |
HART communication | ||
Protocol | HART 7.1, backward compatible | |
Number of devices | up to 8 HART field devices (depending on installation) | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013+A11:2013 | |
Radio and telecommunication terminal equipment | The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning. | |
Directive 2014/53/EU | EN 300 328 V1.8.1:2012 EN 301 489-1 V1.9.2:2011 EN 301 489-17 V2.2.1:2012-09 | |
Conformity | ||
Degree of protection | IEC 60529:2013 | |
Ambient conditions | ||
Ambient temperature | temperature class T5: -40 ... 85 °C (-40 ... 185 °F) temperature class T6: -40 ... 75 °C (-40 ... 167 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Mechanical specifications | ||
Degree of protection | IP67 | |
Material | Aluminum alloy with polyurethane enamel paint | |
Mass | 460 g | |
Dimensions | 60.8 x 60.8 x 100 mm (l x w x h) | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | FM 11 ATEX 0019 X | |
Marking | II 1 G Ex ia IIC T6/T5 Ga II 1 D Ex ia IIIC T95 °C Da | |
Certificate | FM 11 ATEX 0068 X | |
Marking | II 3 G Ex nA IIC T6/T5 Gc | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | CoC3040786(C) | |
Approved for | Class I, Zone 0, (A)Ex ia IIC T6/T5 Ga Class I, Zone 2, (A)Ex nA IIC T6/T5 Gc Class I, Zone 20, (A)Ex ia IIIC T95°C Da Class I, Division 1, Groups A - D Class II, Division 1, Groups E - G Class III Class I, Division 2, Groups A - D | |
IECEx approval | IECEx FMG 11.0010X | |
Approved for | Ex ia IIC T6/T5 Ga Ex nA IIC T6/T5 Gc Ex ia IIIC T95°C Da | |
Standards | IEC 60079-0:2011 , IEC 60079-11:2011 , IEC 60079-15:2010 |
Характеристики
Производитель | Pepperl+Fuchs |
Важная информация
Все информационные материалы, представленные на сайте, носят справочный характер и не могут в полной мере передавать достоверную информацию о свойствах и характеристиках товара.
Фотография на сайте служит дополнительным источником для определения совместимости запчастей с Вашим оборудованием, и не может являться основным. Основной источник по совместимости запчастей - актуальная документация производителя оборудования, из которой значимой информацией для заказа являются: название запчасти и каталожный номер.
Запасные части и комплектующие подбираются самостоятельно покупателем строго по каталожным номерам из официальных деталировок производителей. В случае, если номенклатура товара совпадает с фактически поставленной, но не подходит на оборудование - в ее замене или возврате может быть отказано.
Цены на сайте имеют информационный характер и могут отличаться от цен в коммерческом предложении.
Производитель | Pepperl+Fuchs |