Казань, ул. Мусина, д. 29
kk@promavtomatic.ru

| Производитель | Pepperl+Fuchs |
| Supply | ||
|---|---|---|
| Rated voltage | 24 V DC , in consideration of rated voltage of used isolated barriers | |
| Voltage drop | 0.9 V , voltage drop across the series diode on the termination board must be considered | |
| Ripple | &le 10 % | |
| Fusing | 4 A , in each case for 16 modules | |
| Power dissipation | &le 500 mW , without modules | |
| Reverse polarity protection | yes | |
| Electrical specifications | ||
| volt-free fault indication output | max. 30 V AC/40 V DC, 2 A | |
| Redundancy | ||
| Supply | Redundancy available. The supply for the modules is decoupled, monitored and fused. | |
| Indicators/settings | ||
| Display elements | LEDs PWR ON (Termination Board power supply) - LED power supply I, green LED - LED power supply II, green LED LED FAULT (fault indication), red LED - LED lits: module failure - LED flashes: power supply failure | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2011 For further information see system description. | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | hazardous area connection (field side): spring terminals, blue safe area connection (control side): Yokogawa system connector, 40-pin | |
| Core cross-section | spring terminals: rigid: 0.2 ... 2.5 mm2 flexible: 0.25 ... 1.5 mm2 | |
| Material | housing: polycarbonate, 30 % glass fiber reinforced | |
| Mass | approx. 860 g | |
| Dimensions | 310 x 175 x 153 mm (12.2 x 6.9 x 6.02 inch) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EC-Type Examination Certificate | CESI 11 ATEX 062 | |
| Group, category, type of protection | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I | |
| Safe area | ||
| Maximum safe voltage | 250 V (Attention! Um is no rated voltage.) | |
| Galvanic isolation | ||
| Field circuit/control circuit | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-26:2007 , EN 50303:2000 | |
| International approvals | ||
| IECEx approval | IECEx CES 11.0022 | |
| Approved for | [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I | |
| Производитель | Pepperl+Fuchs |
Все информационные материалы, представленные на сайте, носят справочный характер и не могут в полной мере передавать достоверную информацию о свойствах и характеристиках товара.
Фотография на сайте служит дополнительным источником для определения совместимости запчастей с Вашим оборудованием, и не может являться основным. Основной источник по совместимости запчастей - актуальная документация производителя оборудования, из которой значимой информацией для заказа являются: название запчасти и каталожный номер.
Запасные части и комплектующие подбираются самостоятельно покупателем строго по каталожным номерам из официальных деталировок производителей. В случае, если номенклатура товара совпадает с фактически поставленной, но не подходит на оборудование - в ее замене или возврате может быть отказано.
Цены на сайте имеют информационный характер и могут отличаться от цен в коммерческом предложении.
| Производитель | Pepperl+Fuchs |