Производитель | Pepperl+Fuchs |
General specifications | _x000D_||
---|---|---|
Switching function | _x000D_Normally closed (NC) | _x000D_|
Output type | _x000D_NAMUR | _x000D_|
Rated operating distance | _x000D_4 mm | _x000D_|
Installation | _x000D_non-flush | _x000D_|
Assured operating distance | _x000D_0 ... 3.24 mm | _x000D_|
Actual operating distance | _x000D_3.6 ... 4.4 mm typ. | _x000D_|
Reduction factor rAl | _x000D_0.37 | _x000D_|
Reduction factor rCu | _x000D_0.36 | _x000D_|
Reduction factor r304 | _x000D_0.74 | _x000D_|
Output type | _x000D_2-wire | _x000D_|
Nominal ratings | _x000D_||
Nominal voltage | _x000D_8.2 V (Ri approx. 1 k&Omega) | _x000D_|
Switching frequency | _x000D_0 ... 800 Hz | _x000D_|
Hysteresis | _x000D_1 ... 10 typ. 5 % | _x000D_|
Reverse polarity protection | _x000D_reverse polarity protected | _x000D_|
Short-circuit protection | _x000D_yes | _x000D_|
Current consumption | _x000D__x000D_ | |
_x000D_ | Measuring plate not detected | min. 3 mA | _x000D_
_x000D_ | Measuring plate detected | &le 1 mA | _x000D_
Switching state indicator | _x000D_all direction LED, yellow | _x000D_|
Functional safety related parameters | _x000D_||
MTTFd | _x000D_2520 a | _x000D_|
Mission Time (TM) | _x000D_20 a | _x000D_|
Diagnostic Coverage (DC) | _x000D_0 % | _x000D_|
Compliance with standards and directives | _x000D_||
Standard conformity | _x000D__x000D_ | |
_x000D_ | NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 | _x000D_
_x000D_ | Electromagnetic compatibility | NE 21:2007 | _x000D_
Approvals and certificates | _x000D_||
FM approval | _x000D__x000D_ | |
_x000D_ | Control drawing | 116-0165 | _x000D_
UL approval | _x000D_cULus Listed, General Purpose | _x000D_|
CSA approval | _x000D_cCSAus Listed, General Purpose | _x000D_|
CCC approval | _x000D_CCC approval / marking not required for products rated &le36 V | _x000D_|
Ambient conditions | _x000D_||
Ambient temperature | _x000D_-25 ... 100 °C (-13 ... 212 °F) | _x000D_|
Storage temperature | _x000D_-40 ... 100 °C (-40 ... 212 °F) | _x000D_|
Mechanical specifications | _x000D_||
Connection type | _x000D_cable PVC , 2 m | _x000D_|
Core cross-section | _x000D_0.34 mm2 | _x000D_|
Housing material | _x000D_Stainless steel 1.4305 / AISI 303 | _x000D_|
Sensing face | _x000D_PBT | _x000D_|
Housing diameter | _x000D_12 mm | _x000D_|
Degree of protection | _x000D_IP66 / IP67 | _x000D_|
Cable | _x000D__x000D_ | |
_x000D_ | Bending radius | > 12 x cable diameter | _x000D_
Equipment protection level Dc (tc) | _x000D_||
Instruction | _x000D_Manual electrical apparatus for hazardous areas | _x000D_
|
Device category 3D | _x000D_for use in hazardous areas with combustible dust | _x000D_|
Certificate | _x000D_PF 15CERT3774 X | _x000D_|
CE marking | _x000D_[*PD-Z02585A*] | _x000D_|
ATEX marking | _x000D_![]() The Ex-related marking can also be printed on the enclosed label. | _x000D_
|
Standards | _x000D_EN 60079-0:2012+A11:2013, EN 60079-31:2014 Protection by enclosure tc Some of the information in this instruction manual is more specific than the information provided in the datasheet. | _x000D_
|
General | _x000D_The corresponding datasheets, declarations of conformity, EC-type examination certificates, certifications, and control drawings, where applicable (see datasheets), form an integral part of this document. These documents can be found at www.pepperl-fuchs.com. The maximum surface temperature of the device was determined without a layer of dust on the apparatus. Some of the information in this instruction manual is more specific than the information provided in the datasheet. | _x000D_|
Installation, commissioning | _x000D_Laws and/or regulations and standards governing the use or intended usage goal must be observed. If the Ex-relevant identification is printed exclusively on the adhesive label provided, this label must be affixed in the immediate vicinity of the sensor! The background surface to which the adhesivelabel is to be applied must be clean and free from grease! The applied label must be durable and remain legible, with due consideration of the possibility of chemical corrosion! | _x000D_|
Maintenance | _x000D_No changes can be made to apparatus, which are operated in hazardous areas. Repairs to these apparatus are not possible. | _x000D_
|
Special conditions | _x000D__x000D_ | |
_x000D_ | Minimum series resistance RV | A minimum series resistance RV is to be provided between the power supply voltage and the proximity switch in accordance with the following list. This can also be assured by using a switch amplifier. | _x000D_
_x000D_ | Maximum operating voltage UBmax | The maximum permissible operating voltage UBmax must be restricted to the values given in the following list. Tolerances are not permitted. | _x000D_
_x000D_ | Maximum permissible ambient temperature TUmax | Values can be obtained from the following list, depending on the max. operating voltage Ub max and the minimum series resistance Rv. | _x000D_
_x000D_ | at UBmax=9 V, RV=562 &Omega | 61 °C (141.8 °F) | _x000D_
_x000D_ | using an amplifier in accordance with EN 60947-5-6 | 61 °C (141.8 °F) | _x000D_
_x000D_ | Protection from mechanical danger | The sensor must not be exposed to ANY FORM of mechanical danger. | _x000D_
_x000D_ | Protection from UV light | The sensor and the connection cable must be protected from damaging UV-radiation. This can be achieved when the sensor is used in internal areas. | _x000D_
_x000D_ | Protection of the connection cable | The connection cable must be prevented from being subjected to tension and torsional loading. | _x000D_
_x000D_ | Electrostatic charge | Electrostatic charges must be avoided on the mechanical housing components. Dangerous electrostatic charges on the mechanical housing components can be avoided by incorporating these in the equipotential bonding. Do not attach the nameplate provided in areas where electrostatic charge can build up. | _x000D_
General information | _x000D_||
Scope of delivery | _x000D_2 self locking nuts in scope of delivery | _x000D_|
Use in the hazardous area | _x000D_see instruction manuals | _x000D_|
_x000D_ | Category | 1G 2G 3G 1D 3D | _x000D_
Фото актуальное | Да |
Производитель | Pepperl+Fuchs |
Все информационные материалы, представленные на сайте, носят справочный характер и не могут в полной мере передавать достоверную информацию о свойствах и характеристиках товара.
Фотография на сайте служит дополнительным источником для определения совместимости запчастей с Вашим оборудованием, и не может являться основным. Основной источник по совместимости запчастей - актуальная документация производителя оборудования, из которой значимой информацией для заказа являются: название запчасти и каталожный номер.
Запасные части и комплектующие подбираются самостоятельно покупателем строго по каталожным номерам из официальных деталировок производителей. В случае, если номенклатура товара совпадает с фактически поставленной, но не подходит на оборудование - в ее замене или возврате может быть отказано.
Цены на сайте имеют информационный характер и могут отличаться от цен в коммерческом предложении.
Фото актуальное | Да |
Производитель | Pepperl+Fuchs |
© 2025 ООО «Компказань», все права защищены
Политика в отношении обработки персональных данных и данных cookie