Компонент аналогового входа Transmitter Power Supply KFU8-CRG2-Ex1.D Pepperl+Fuchs
Производитель | Pepperl+Fuchs |
Описание товара
General specifications | ||
---|---|---|
Signal type | Analog input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | terminals 23, 24 | |
Rated voltage | 20 ... 90 V DC or 48 ... 253 V AC | |
Power dissipation | 2 W / 3 VA | |
Power consumption | 2.2 W / 4 VA | |
Interface | ||
Programming interface | programming socket | |
Input | ||
Connection side | field side | |
Connection | terminals 1, 2, 3 | |
Input I | ||
Input signal | 0/4 ... 20 mA | |
Available voltage | > 15 V at 20 mA | |
Open circuit voltage/short-circuit current | 24 V / 33 mA | |
Input resistance | 45 &Omega (terminals 2, 3) | |
Line fault detection | breakage I < 0.2 mA short-circuit I > 22 mA | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 10, 11, 12 output II: terminals 16, 17, 18 output III: terminals 8+, 7- | |
Output signal | 0 ... 20 mA or 4 ... 20 mA | |
Output I, II | signal, relay | |
Contact loading | 250 V AC / 2 A / cos &phi &ge 0.7 40 DC / 2 A | |
Mechanical life | 5 x 107 switching cycles | |
Output III | Signal, analog | |
Current range | 0 ... 20 mA or 4 ... 20 mA | |
Open loop voltage | max. 24 V DC | |
Load | max. 650 &Omega | |
Fault signal | downscale I &le 3.6 mA, upscale I &ge 21.5 mA (acc. NAMUR NE43) | |
Indicators/settings | ||
Display elements | LEDs , display | |
Control elements | Control panel | |
Configuration | via operating buttons via PACTware | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | 300 g | |
Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | TÜV 01 ATEX 1701 | |
Marking | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 | |
International approvals | ||
FM approval | ||
Control drawing | 16-554FM-12 (cFMus) | |
IECEx approval | IECEx TUN 09.0007 | |
Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
Характеристики
Производитель | Pepperl+Fuchs |
Важная информация
Все информационные материалы, представленные на сайте, носят справочный характер и не могут в полной мере передавать достоверную информацию о свойствах и характеристиках товара.
Фотография на сайте служит дополнительным источником для определения совместимости запчастей с Вашим оборудованием, и не может являться основным. Основной источник по совместимости запчастей - актуальная документация производителя оборудования, из которой значимой информацией для заказа являются: название запчасти и каталожный номер.
Запасные части и комплектующие подбираются самостоятельно покупателем строго по каталожным номерам из официальных деталировок производителей. В случае, если номенклатура товара совпадает с фактически поставленной, но не подходит на оборудование - в ее замене или возврате может быть отказано.
Цены на сайте имеют информационный характер и могут отличаться от цен в коммерческом предложении.
Производитель | Pepperl+Fuchs |