Датчик предельной ёмкости Capacitive limit switch LCL1 Pepperl+Fuchs

Кат. номер: 271947
Наличие: Под заказ, срок отгрузки от 5-7 дней
Стоимость: По запросу
Узнать стоимость и срок поставки

Описание товара

General specifications
Measuring methodA metal plate at the end of the probe, within the insulation, and the surroundings (e. g. the silo walls) combine to form the two electrodes of a capacitor. If the probe is covered or free of material, then the capacitance changes and the LCL switches.
Equipment architectureThe measuring system consists of:
- the device
- a supply point
- the connected control systems, switching units, signalling systems (e. g. lamps, horns, PCS, PLC, etc.)
Construction typedevice with rod probe
Operating modeMAX = maximum safety:
The device switches if the probe is covered or if the supply voltage is disconnected in a safety-oriented manner (signal on alarm).
example application: overspill protection
MIN = minimum safety:
The device switches if the probe is uncovered or if the supply voltage is disconnected in a safetyoriented manner (signal on alarm).
example application: dry-running protection
Supply
Rated voltageelectrical connection E5: 10.8 ... 45 V DC, short-term pulse on 55 V DC
electrical connection WA: 20 ... 235 V AC, 50/60 Hz or 20 ... 55 V DC
Current consumptionelectrical connection E5: max. 30 mA, reverse-polarity-proof
electrical connection WA: max. 130 mA
Electrical specifications
Surge protectionovervoltage category III
Input
Measured variablelimit level (limit value)
Measurement rangedielectric constant &ge 1.6
Output
Output signalconnection E5: switching PNP, Imax = 200 mA
- overload and short circuit protection
- residual voltage at transistor at Imax < 2.9 V
connection WA: contact change-over, potential-free
- Umax = 253 V
- Imax = 4 A (AC)
- Pmax = 1000 VA, cos &phi = 1, Pmax = 500 VA, cos &phi > 0.7
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2006 , EN 61326-2-3:2006
Low voltage
Directive 2014/35/EUEN 61010-1:2010
Conformity
Electromagnetic compatibilityNE 21
Degree of protectionIEC 60529:2001
Vibration resistanceEN 60068-2-64
Climate classEN 60068, part 2-38 (test Z/AD)
Measurement accuracy
Reference operating conditionsvessel type: plastic vessel, ambient temperature: 73 °F (23 °C, 296 K), medium temperature: 73 °F (23 °C, 296 K)
medium pressure pe: 0 bar, medium: dielectric constant = 2.6, conductivity: < 1 &microS
sensitivity setting: C
Hysteresishorizontal 4 mm (0.16 inch), vertical 7 mm (0.28 inch)
Long-term drifthorizontal 3 mm (0.12 inch), vertical 6 mm (0.24 inch)
Influence of medium temperaturedepending on the filling material
Switching timeapprox. 0.5 s when covering and uncovering the sensor
Operating conditions
Installation conditions
Installation positionany position
Mounting locationThe capacitive limit switch can be installed in silos made of different materials (e. g. metal, plastic, concrete).
Process conditions
Process temperature-40 ... 130 °C (-40 ... 266 °F)
-40 ... 80 °C (-40 ... 176 °F) (Dust-Ex version)
Medium pressure limits-1 ... 25 bar
State of aggregationfluids and solids
Solid contents&le &empty 30 mm
Bulk density&le 200 g/l
Ambient conditions
Ambient temperature-40 ... 80 °C (-40 ... 176 °F)
-40 ... 60 °C (-40 ... 140 °F) (Dust-Ex version)
Storage temperature-40 ... 80 °C (-40 ... 176 °F)
Shock resistancedevice with F34 housing: 7 J
Vibration resistancea(RMS) = 50 m/s2, ASD = 1.25 (m/s2)2/Hz, f = 5 to 2000 Hz, t = 3 x 2 h
Mechanical specifications
Degree of protectionIP66, NEMA 4
Connectiongland M20
thread G1/2, NPT1/2
MaterialF14 housing: polyester PBT-FR
F34 housing F34: aluminum
Probe: PPS GF40
Dimensionsmax. &empty94 mm (3.7 inch), length 391 mm (15.4 inch)
Process connectionthread R1 acc. to EN 10226, BSPT, adapter for R1-1/2 and G1-1/2 see accessories
thread NPT1 to ANSI B 1.20.1, adapter for NPT1-1/4 see accessories
Data for application in connection with hazardous areas
EU-Type Examination Certificatesee instruction manuals (SI)
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-31:2009
Accessories
Optional accessoriesLCL-Z10 cover with sight glass for F14 housing
LCL-Z11 adapter for R1-1/2, EN 10226
LCL-Z12 adapter for G1-1/2, DIN ISO 228
LCL-Z13 adapter for NPT1-1/4, steel
LCL-Z15 adapter for NPT1-1/4, 1.4571

Характеристики

Производитель Pepperl+Fuchs

 

Важная информация

Все информационные материалы, представленные на сайте, носят справочный характер и не могут в полной мере передавать достоверную информацию о свойствах и характеристиках товара.

Фотография на сайте служит дополнительным источником для определения совместимости запчастей с Вашим оборудованием, и не может являться основным. Основной источник по совместимости запчастей - актуальная документация производителя оборудования, из которой значимой информацией для заказа являются: название запчасти и каталожный номер.

Запасные части и комплектующие подбираются самостоятельно покупателем строго по каталожным номерам из официальных деталировок производителей. В случае, если номенклатура товара совпадает с фактически поставленной, но не подходит на оборудование - в ее замене или возврате может быть отказано.

Цены на сайте имеют информационный характер и могут отличаться от цен в коммерческом предложении.

Производитель Pepperl+Fuchs
×
Для заказа продукции свяжитесь с нами любым удобным Вам способом. Или заполните онлайн-форму, и мы сразу ответим Вам в рабочее время
Елин Руслан, руководитель отдела продаж
Технический отдел
Казань, Адоратского, 34
KompKZN@promavtomatic.ru
Image