Устройство защиты Fieldbus Surge Protector, Cabinet Installation, Ex ia DP-LBF-I1.36.* Pepperl+Fuchs
Производитель | Pepperl+Fuchs |
Описание товара
General specifications | ||
---|---|---|
Design / Mounting | Cabinet installation | |
Electrical specifications | ||
Rated voltage | 33 V | |
Rated current | 500 mA | |
Voltage protection level | ||
Line/Line | max. 58 V category C1/C2 8/20µsec max. 50 V category C3 1kV/µsec max. 51 V category B2 10/700µsec max. 55 V category D1 10/350µsec | |
Line/Earth | max. 1400 V category C1/C2 8/20µsec max. 1100 V category C1/C2 1kV/µsec max. 1000 V category B2 10/700µsec max. 1300 V category D1 10/350µsec | |
Screen/Shield directly grounded | max. 25 V category C1/C2 8/20µsec max. 20 V category D1 10/350µsec | |
Screen/Shield indirectly grounded (via GDT) | max. 700 V category C1/C2 8/20µsec max. 600 V category C3 1kV/µsec max. 500 V category B2 10/700µsec max. 600 V category D1 10/350µsec | |
Reaction time | ||
Line/Line | max. 1 ns | |
Line/Earth | max. 100 ns | |
Screen/Shield-Earth | max. 100 ns | |
Overstressed fault mode | acc. IEC 61643-21 line inoperable mode 3 lines 1 and 2 at 15,5kA (8/20µsec) lines 3 and 4 at 30kA (8/20µsec) | |
Series resistance in line | 1 &Omega +/- 5 % | |
Impulse durability | ||
Per line | 1 kA category D1 10/350µsec , 5 kA category C1/C2 8/20µsec | |
Screen/Shield directly grounded | 5 kA category D1 10/350µsec | |
Screen/Shield indirectly grounded (via GDT) | 4 kA category D1 10/350µsec , 10 kA category C1/C2 8/20µsec | |
Capacitance | ||
Line/Line | 800 pF | |
Line/Earth | 16 pF | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 | |
Standard conformity | ||
Degree of protection | IEC 60529 | |
Fieldbus standard | IEC 61158-2 | |
Climatic conditions | IEC 60721 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Surge protection | IEC 61643-21 | |
Ambient conditions | ||
Ambient temperature | -50 ... 80 °C (-58 ... 176 °F) | |
Storage temperature | -50 ... 85 °C (-58 ... 185 °F) | |
Relative humidity | &le 95 % non-condensing | |
Shock resistance | 15 g 11 ms | |
Vibration resistance | 1 g , 10 ... 150 Hz | |
Mechanical specifications | ||
Connection type | screw terminals | |
Core cross-section | flexible wire 2.5 mm2 solid wire max. 4 mm2 | |
Housing material | Polyamide PA 6.6 | |
Degree of protection | IP20 | |
Mass | Protection Module 20 g , base module 40 g | |
Mounting | 35 mm DIN mounting rail | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | KEMA 09 ATEX 0191 X | |
Marking | II 2(1)G Ex ia [ia Ga] IIC T4/T5/T6 Gb | |
Voltage | 30 V | |
Current | 500 mA | |
Internal capacitance | negligible 0 nF | |
Internal inductance | negligible 0 µH | |
Certificate | KEMA 09 ATEX 0190 X | |
Marking | II 3G Ex ic IIC T4/T5/T6 Gc , II 3G Ex nA IIC T4/T5/T6 Gc | |
Voltage | 33 V | |
Current | 500 mA | |
Internal capacitance | negligible 0 nF | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 , EN 60079-26:2007 | |
International approvals | ||
CSA approval | CSA 2437472 | |
Control drawing | 116-0361 | |
Approved for | Class I, Zone 1, AEx/Ex ia IIC T4...T6, Class I, Zone 2, AEx nC IIC T4...T6, Class I, Zone 2, Ex nL IIC T4...T6, Class I, Zone 2, AEx/Ex nA IIC T4...T6 Class I Div. 1, GP A, B, C, D T4...T6, Class I Div. 2, GP A, B, C, D T4...T6, Class I Div. 2, GP A, B, C, D T4...T6 | |
IECEx approval | IECEx KEM 09.0088X | |
Approved for | Ex ia [ia Ga] IIC T4/T5/T6 Gb , Ex ic IIC T4/T5/T6 Gc , Ex nA IIC T4/T5/T6 Gc | |
Certificates and approvals | ||
Marine approval | pending |
Характеристики
Производитель | Pepperl+Fuchs |
Важная информация
Все информационные материалы, представленные на сайте, носят справочный характер и не могут в полной мере передавать достоверную информацию о свойствах и характеристиках товара.
Фотография на сайте служит дополнительным источником для определения совместимости запчастей с Вашим оборудованием, и не может являться основным. Основной источник по совместимости запчастей - актуальная документация производителя оборудования, из которой значимой информацией для заказа являются: название запчасти и каталожный номер.
Запасные части и комплектующие подбираются самостоятельно покупателем строго по каталожным номерам из официальных деталировок производителей. В случае, если номенклатура товара совпадает с фактически поставленной, но не подходит на оборудование - в ее замене или возврате может быть отказано.
Цены на сайте имеют информационный характер и могут отличаться от цен в коммерческом предложении.
Производитель | Pepperl+Fuchs |