Казань, Адоратского, 34
KompKZN@promavtomatic.ru

Производитель | Pepperl+Fuchs |
General specifications | ||
---|---|---|
Measuring method | A piezoelectric drive excites the vibrating rod of the device to its resonance frequency. If medium covers the vibrating rod, the rod`s vibrating amplitude changes (the vibration is damped). The electronics of the device compare the actual amplitude with a target value and indicates whether the vibrating rod is vibrating freely or whether it is covered by medium. | |
Equipment architecture | The measuring system consists of: - the device with electronic insert - a supply point - the connected control systems, switching units, signalling systems (e. g. lamps, horns, PCS, PLC, etc.) | |
Construction type | compact device | |
Operating mode | MAX = maximum safety: The device switches if the probe is covered or if the supply voltage is disconnected in a safety-oriented manner (signal on alarm). example application: overspill protection MIN = minimum safety: The device switches if the probe is uncovered or if the supply voltage is disconnected in a safetyoriented manner (signal on alarm). example application: dry-running protection | |
Supply | ||
Rated voltage | electronic insert FEM22 (E5): 10 ... 45 V DC electronic insert FEM24 (WA): 19 ... 253 V AC, 50/60 Hz or 19 ... 55 V DC | |
Ripple | electronic insert FEM22 (E5): max. 5 V, 0 ... 400 Hz | |
Current consumption | electronic insert FEM22 (E5): max. 18 mA | |
Reverse polarity protection | separation voltage 2.2 kV | |
Electrical specifications | ||
Surge protection | electronic insert FEM22 (E5) : overvoltage category III | |
Input | ||
Input signal | probe covered - small amplitude probe not covered - large amplitude | |
Measured variable | level (according to the mounting location and the overall length) | |
Measurement range | The measuring range depends on the mounting location of the device | |
Output | ||
Output signal | digital | |
Galvanic isolation | ||
Input/Other circuits | electronic insert FEM24 (WA) | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2006 , EN 61326-2-3:2006 | |
Low voltage | ||
Directive 2014/35/EU | electronic insert FEM24 (WA) : EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21 | |
Degree of protection | IEC 60529:2001 | |
Vibration resistance | EN 60068-2-27 | |
Climate class | EN 60068, part 2-38, fig. 2a | |
Measurement accuracy | ||
Measuring frequency | 700 ... 800 Hz | |
Switching time | when covering the sensor approx. 0.5 s, when uncovering the sensor approx. 1.0 s | |
Operating conditions | ||
Installation conditions | ||
Installation position | see section mounting position | |
Process conditions | ||
Process temperature | -40 ... 150 °C (-40 ... 302 °F) | |
Medium pressure limits | -1 ... 25 bar max. working pressure 25 bar, burst pressure 100 bar | |
Thermal shock resistance | max. 120 K | |
State of aggregation | solids | |
Solid contents | &le &empty25 mm | |
Bulk density | &ge 200 g/l, not fluidised | |
Ambient conditions | ||
Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Mechanical specifications | ||
Degree of protection | IP66/IP67, NEMA 4X | |
Connection | gland M20 thread G1/2, NPT1/2 | |
Material | F16 housing: PTB-FR, cover with transparent glass made of PA12, EPDM cover seal F18 housing: aluminum EN-AC-AlSi10Mg, plastic coated cover seal: EPDM process connections, sensor: stainless steel 1.4435/316L | |
Mass | device with F16 housing, electronic insert FEM24 (WA) and R1 thread: approx. 1.0 kg | |
Dimensions | max. &empty85 mm (3.3 inch), length 372 mm (14.6 inch) | |
Process connection | thread R1, R1-1/2 acc. to DIN 2999 thread 1-1/4 - 11-1/2 NPT, 1-1/2 - 11-1/2 NPT acc. to ANSI B 1.20.1 | |
Data for application in connection with hazardous areas | ||
EC-Type Examination Certificate | KEMA 06 ATEX 0055 | |
Group, category, type of protection | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-31:2009 | |
International approvals | ||
IECEx approval | IECEx DEK 11.0068 | |
Approved for | Ex ta/tc IIIC T170°C Da/Dc |
Производитель | Pepperl+Fuchs |
Все информационные материалы, представленные на сайте, носят справочный характер и не могут в полной мере передавать достоверную информацию о свойствах и характеристиках товара.
Фотография на сайте служит дополнительным источником для определения совместимости запчастей с Вашим оборудованием, и не может являться основным. Основной источник по совместимости запчастей - актуальная документация производителя оборудования, из которой значимой информацией для заказа являются: название запчасти и каталожный номер.
Запасные части и комплектующие подбираются самостоятельно покупателем строго по каталожным номерам из официальных деталировок производителей. В случае, если номенклатура товара совпадает с фактически поставленной, но не подходит на оборудование - в ее замене или возврате может быть отказано.
Цены на сайте имеют информационный характер и могут отличаться от цен в коммерческом предложении.
Производитель | Pepperl+Fuchs |
© 2025 ООО «Компказань», все права защищены
Политика в отношении обработки персональных данных и данных cookie